A ground source heat pump (GSHP) is a heating and cooling system
that transfers heat to or from the ground, using the ground as a
heat sink in the summer and heat source in the winter. Like
air-source heat pumps, GSHPs use a reversible refrigeration cycle
to provide heating and cooling. A ground source heat pump can be
significantly more energy efficient than an air source heat pump
because outside air temperatures vary by as much as 100°F from
winter to summer. At either temperature extreme, an air
source heat pump is not efficient in transferring heat.
In comparison, ground temperatures may vary by as little as 10°F
from winter to summer. This temperature stability means that
system efficiencies remain steady during times of significant
heating or cooling demand, in contrast to air source heat pumps
whose efficiencies can drop during extreme weather events when
demand is the greatest.
| Figure 1 - Ground Source Heat Pump |
|
This diagram depicts a ground source heat pump in cooling mode.
GSHPs use a reversible refrigeration cycle to provide either
heating or cooling to a building.
|
Careful planning and engineering design needs to be performed to
determine if a building and site are appropriate for a
ground-source heat pump. A geotechnical engineer should
evaluate subsurface conditions on the site. Test borings may
be used to identify soil conditions, rock strata, and the presence
of water. The heat transfer properties of these materials must also
be evaluated so that the system can be designed to function
properly for many years. The geotechnical engineering and the
heat exchanger installation are significant reasons why ground
source heat pump systems can have much higher installation costs
than competing systems.
| Figure 2 - Ground Source Heat Pump Energy Comparison Chart |
|
The U. S. Department of Energy report notes that "the modeled 2.9
coefficient of performance (COP) heating efficiency of the
air-source heat pump is halfway between the cold weather (17°F) and
standard, mild weather (47°F) rating conditions of a new
high-efficiency (FEMP-recommended and ENERGY STAR model).
Similarly, the modeled cooling efficiencies of the air-source heat
pump, gas furnace, and air-source air conditioner all represent
models that just meet the FEMP-recommended and ENERGY STAR
qualifying levels." Original site energy use data converted to
source energy use per EPA national conversion factors of 3.34
source kBtu per site kBtu for electricity use and 1.047 source kBtu
per site kBtu for natural gas use.
|
Basic Concepts
- Geothermal energy is a term which describes
the "heat from the earth". At 10 feet below the earth's
surface, the ground temperature remains nearly constant all
year. In winter the earth is warmer than the outside air
temperature, and in summer the earth is cooler than the outside air
temperature.
- The term "ground source heat pump" (GSHP)
describes various types of vapor compression-based space
conditioning equipment that use a geothermal resource - such
as the earth, ground water, or surface water - as a source of heat
in winter and a sink for heat in the summer. Ground source
heat pumps use reversible refrigerant cycles to provide either
heating or cooling as required by the building.
- The components of a GSHP system are the heat
exchanger that is surrounded by earth or water, the compressor, and
the heat exchanger in the air distribution system. In a
direct exchange system, the heat exchanger in the ground,
typically comprised of copper tubing, is used as an evaporator in
the heating mode and as a condenser in the cooling mode. Similarly,
the coil in the air distribution system is a condenser during
heating and an evaporator during cooling. Direct exchange systems
are more efficient than indirect systems that use water loops since
the refrigerant directly exchanges heat with the ground without the
need for a refrigerant-water heat exchanger. Most systems are
indirect and consist of two loops: a refrigerant loop that
is contained within the heat pump cabinet and a secondary water
loop that circulates a water-antifreeze mixture through the ground
heat exchanger. Indirect systems are less efficient at
transferring heat and require larger land areas for the ground heat
exchanger than direct systems, but piping costs are lower than
direct system piping costs since they generally use some type of
plastic piping rather than copper.
The benefits of a ground source heat pump system are illustrated
by a U. S. Department of Energy analysis of a 25,000 square foot
office building in Washington, DC. The analysis concluded that
"the biggest benefit of ground source heat pumps is that they use
25%-50% less electricity than conventional heating or cooling
systems. This translates into a GSHP using one unit of electricity
to move three units of heat from (or to) the earth. According to
the EPA, geothermal heat pumps can reduce energy consumption-and
corresponding emissions-up to 44% compared to air-source heat pumps
and up to 72% compared to electric resistance heating with standard
air-conditioning equipment."
The Figure 2 GSHP Energy Comparison Chart was developed from
data included in the U. S. Department of Energy analysis. The
chart provides a comparison of annual energy use for an Air-Source
Heat Pump (ASHP), a Gas Furnace with Air Conditioning, an
"energy-efficient" Ground Source Heat Pump, and a "Best Available"
Ground Source Heat Pump.
Because GSHP systems better maintain their efficiency levels
during temperature extremes compared to air source heat pumps, GSHP
systems can also provide significant savings in electric utility
demand charges compared to air source heat pumps and comparable A/C
systems.
Proper design of the piping system is critical to the success of
the project. Piping will vary depending on soil conditions
and heat pump design. Piping may include horizontal or
vertical fields (vertical shafts or wells). A lake, pond, or
reservoir may also be a geothermal source, or sink, for heating or
cooling a nearby facility. Piping design may be a closed loop
system, which circulates water, or water mixed with
anti-freeze. Piping may also be connected to an open well
system that pumps ground water through the system and discharges it
back to the ground or to a surface reservoir.
| Figure 3 - Ground Source Heat Pump Coil |
A model two-story school with 100,000 square feet is situated
adjacent to play fields which accommodate 88,000 square feet
(approximately 2 acres) of horizontally coiled piping, which is
covered by at least six feet of soil, which was stockpiled on the
site. Installation costs were reduced by installing the piping as
the site was graded in preparation for building construction. The
model two-story school has a central air distribution system, a
heat recovery system, and a two-pipe water distribution system. The
heat recovery system collects heat from exhaust air before it is
discharged from the building. This heat is then used to temper
outside air before it is distributed to each space. A heat pump is
provided for each classroom, and other larger spaces, and is
mounted in the branch supply air duct, which serves that space.
Water is pumped from the exterior field to the heat pumps to meet
heating or cooling demands. Then, the water is re-circulated
through the field again. The configuration of this system provides
individual room temperature control for each major space in the
building.
|

Photograph Credit: Air
Solutions |
The piping itself can be relatively inexpensive, such as
high-density polyethylene (HDPE) tubing. At the same time,
vertical boring and horizontal excavation can be relatively
expensive. Vertical borings may be filled with a thermally
conductive grout after the piping is installed. This is an
important detail to be considered in the design of the piping
system.
The piping configuration is frequently influenced by the size of
the building, the amount of land available, and surface
improvements. If the building footprint is relatively small,
land is plentiful, and trenching can be accomplished without
disturbing existing trees and shrubs, a horizontal field may be a
relatively inexpensive solution. If the building footprint is
large, land is limited, and trees and shrubs limit trenching or
excavation, deep vertical borings may be required around the
building to accommodate vertical wells. For instance, Oak
Ridge National Laboratory estimates that 1500 ft2 to
3000 ft2 of land area is required per ton of cooling for
horizontal fields, while vertical borings typically require 250
ft2 to 300 ft2 of land area per
ton1. Coordination of this work with site grading or
foundation excavation is important to provide access for boring
equipment and minimize installation costs.
The integration of ground source heat pumps with heating,
ventilation, and air conditioning distribution systems may vary by
building type and climate conditions. The heat exchanger may
be water-to-water or water-to-air. Air systems are commonly
used, but there are applications for hydronic systems also. The
size and number of heat pumps is also dependent on the building
type and the size of spaces being served. The various
options, combinations, and configurations are a topic for another
discussion.
1. Shonder, John A., Geothermal Heat
Pumps for School Applications, Rebuild America Geothermal
Workshop, March 5, 2002
| Training Highlights |
|
California utilities offer outstanding educational opportunities
that focus on the design, construction and operation of
energyefficient buildings. Listed here are a few of the many
upcoming classes and events; for complete schedules, visit each
utility's website.
Integrating Energy Efficiency and Renewables in
Commercial Retrofits
This course will focus on decreasing energy use through a
whole-system approach to buildings, using the best combination of
technologies to lower a building's energy footprint. The instructor
will cover the science of building performance, energy efficiency
measures, and renewable energy systems. PEC. June 15, 9am - 12pm,
San Francisco. (Course also offered for Home Retrofits: June 11,
9am - 4:30pm, Santa Cruz Police Department.)
register >
|
Kensington Clean Energy Festival
This free public event features information on property assessed
clean energy loans for the installation of solar electric, solar
water heating systems, energy efficiency and water savings
technologies. June 26, 10:30am - 2:30pm, 4121 Adams Avenue, San
Diego.
register >
Save Energy, Save Money: An Introduction to Energy
Efficiency and Rebates
Learn how to save money on lighting, air conditioning, motors,
controls, refrigeration, and other equipment. Course includes how
to complete your own energy audit, ways to reduce energy usage and
how to use rebates and incentives to help reduce costs. Southern
California Edison, CTAC. July 13, 8:30am - 12:30pm, Irwindale.
register >
|
Don't miss future issues - to sign up for a free email subscription, please visit our
newsletter subscription page. Send letters to the editor, suggestions on topics for future
issues, or other comments to the e-News editor via our
Comments & Feedback form.
e-News is published by Energy Design
Resources (www.energydesignresources.com),
an online resource center for information on energy efficiency design practices in
California.
Savings By Design (www.savingsbydesign.com)
offers design assistance and incentives to design teams and building owners in California
to encourage high-performance nonresidential building design and construction.
Energy Design Resources and Savings By Design are funded by California utility customers
and administered by Pacific Gas and Electric Company, Sacramento Municipal Utility
District, San Diego Gas and Electric, Southern California Edison and Southern California
Gas Company, under the auspices of the California Public Utilities Commission.